- Rated power
- 50 kW
- System capacity
- 100 kWh
- Architecture
- All-in-one, DC-coupled; factory pre-integrated (plug-and-play)
- On/off-grid switching
- Within 20 ms
- Black start
- Self-starting without grid or solar power
- Max. PV array power
- 100 kWp @STC
- Max. DC voltage
- 1000 V
- MPPT voltage range
- 180–850 V
- Generator
- Generator interface
- Max. generator input power
- 138 kW
- Battery cell
- 314 Ah
- Chemistry
- LFP
- Single-cabinet expansion
- From 2 h to 8 h (50 kW / 400 kWh)
- Optional battery cabinet
- BC100: 100 kWh, LiFePO4 314 Ah, smoke and temperature sensors + aerosol
- Surge protection
- Type II SPD on AC and DC sides
- Arc fault
- AFCI
- Detection
- Smoke detector, temperature sensor, combustible gas detector
- Ventilation
- Integrated with combustible gas detection
- Alarm
- Audible and visual alarm
- Fire
- Aerosol fire extinguisher; gel fire suppression in the battery compartment
- MPPTs
- 6, with 2 strings each (12 strings)
- Max. DC input current
- 6 × 45 A
- Battery protection
- IP55, C3/C4 corrosion resistance
- Inverter protection
- IP66
- Operating temperature
- −30 °C to 50 °C (derating from 45 °C to 50 °C)
- Cooling
- HVAC (battery) / smart fan cooling (inverter)
- Parallel operation
- Up to 10 cabinets (500 kW / 1 MWh)